Experimental and numerical study on the thermal environment of a data center

期刊

BUILDING AND ENVIRONMENT
卷 212, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2021.108741

关键词

Data center; Field experiment; Thermal environment; Energy saving; Numerical simulation

资金

  1. National Natural Science Foundation of China [51778080]

向作者/读者索取更多资源

This study conducted field experiments and thermal environment evaluation in an existing data center. Problems were identified and three cost-efficient methods were proposed and validated through simulation and field experiments. The results showed significant improvement in the thermal environment and energy savings.
Data centers are energy-intensive facilities, and a suitable thermal environment is vital for the safe and reliable operation of information technology equipment and energy saving. In this case study, field experiments and thermal environment evaluation were conducted in an existing data center. However, some problems were reported, including the relative humidity of the rack inlet air exceeding 60%, hot-cold air mixing, non-uniform temperature distribution, local overheating, and a low average temperature difference between the return and supply air of computing room air conditioning units (CRACs). To overcome these dilemmas, three cost-efficient and convenient methods for improving the thermal environment were proposed, including installing blanking panels, closing unnecessary perforated tiles, and increasing the set return air temperature of CRACs. The temperature field and flow field were simulated using the software 6SigmaRoom to predict the effects of the optimization methods. Finally, after the optimization scheme was implemented, field experiments were performed again to examine the application effects of optimization measures. The results demonstrate that the temperature distribution was more uniform, and the thermal environment was considerably improved. Meanwhile, the average temperature difference between the return and supply air of CRACs increased from 6.7 degrees C to 8.8 degrees C, resulting in a decrease in the supply air volume of CRACs of about 10903.37 m(3)/h, and saving the energy consumption of the fans around 96 kWh/day.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据