4.7 Article

Implementation of a coupled simulation framework with neural network and Modelica for fast building energy simulation considering non-uniform indoor environment

期刊

BUILDING AND ENVIRONMENT
卷 211, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2021.108740

关键词

Coupled simulation framework; Neural network; Modelica; Non-uniform indoor environment; Energy simulation

向作者/读者索取更多资源

The coupling of CFD and BES enables simultaneous consideration of indoor environment quality and building energy performance in architecture design. In this study, an innovative coupled simulation framework using a neural network for fast and accurate prediction of indoor air distribution is proposed. The framework demonstrates more reasonable results and significantly reduces calculation time compared to traditional coupled simulation methods.
The coupling of computational fluid dynamics (CFD) and building energy simulation (BES) program enables the simultaneous consideration of the indoor environment quality and building energy performance in architecture design. Meanwhile, it improves the energy simulation accuracy for non-uniform indoor environments as compared to a standalone BES. However, a CFD-BES coupled simulation confronts a great challenge in that conducting high-fidelity CFD simulations is time-consuming, making it impractical for scenarios requiring a large number of CFD executions. In this study, an innovative coupled simulation framework is proposed and implemented for fast energy simulation considering non-uniform indoor environments. As a surrogate for CFD, a neural network (NN) for achieving a fast and accurate prediction of the indoor air distribution is coupled with a Modelica-based energy simulation program. The crucial functionality of the coupled simulation framework is validated against the results of a coupled simulation between fast fluid dynamics (FFD) and Modelica. Furthermore, the framework is tested with a more complicated case to explore its feasibility and potential for practical applications. Compared to a standalone BES, the coupled simulation considering a non-uniform environment demonstrates more reasonable results regarding heat transfer calculations and system operations. Moreover, the proposed framework requires only 52 s to execute a simulation with a physical process of 24 h, resulting in an approximately 94% reduction in calculation time relative to a coupled simulation between CFD and BES.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据