4.5 Article

Experimental investigation on NH3-H2O compression-assisted absorption heat pump (CAHP) for low temperature heating in colder conditions

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2016.03.019

关键词

Low temperature heating; Absorption heat pump; Ammonia-water; Compression-assisted absorption; Experimental investigation; Cold regions

资金

  1. Innovative Research Groups of the National Natural Science Foundation of China [51521005]

向作者/读者索取更多资源

The coefficient of performance (COP) and heating capacity of the absorption heat pump (AHP) decreased obviously as the evaporator inlet temperature dropped. Compression-assisted AHP (CAHP) could operate efficiently in colder conditions, and a prototype was constructed for experimental investigation. At a generator inlet of 130 degrees C, as the evaporator inlet decreases from -5 degrees C to -25 degrees C, the COP drops from 1.513 to 1.372, while the heating capacity deteriorates from 77.26 kW to 47.11 kW. Comparisons between CARP and normal AHP indicated that CAHP can extend the lower limit of evaporator inlet temperature from -10 degrees C to -25 degrees C. Besides, CAHP can enhance the heating capacity by approximately 55.5-85.0% even when AHP can operate normally. Moreover, the improvement contributed by CARP is greater under much colder conditions. The heating COP and capacity of CAHP are improved in all the conditions, while the primary energy efficiency is advantageous under lower evaporator inlet temperatures. (C) 2016 Elsevier Ltd and IIR. All rights reserved.