Analysis on key influence factors of air source heat pumps with field monitored data in Beijing

出版社

ELSEVIER
DOI: 10.1016/j.seta.2021.101642

关键词

Air source heat pump; Seasonal coefficient of system performance; Field monitored; Terminal types; Operating load rate

资金

  1. National Key RD Plan of China [2019YFE0103000]
  2. Science and Technology Project of the Ministry of Housing and Urban-Rural Development of People's Republic of China [2021-K-161]

向作者/读者索取更多资源

Field monitoring and decoupling analysis of 103 ASHP systems in Beijing during the 2018-2019 heating season identified three key influencing factors on performance: terminal type, operating load rate, and capacity regulation characteristics. Floor heating systems had a higher SCOP due to lower water temperature compared to radiator systems. Oversized capacity was a common issue, leading to increased energy consumption and power usage by the circulating pump.
Air source heat pumps (ASHPs) are in wide use around the world, and their practical applications and continual improvement have attracted great attention. To more fully understand their actual-operational performance, field monitoring was carried out on 103 ASHP systems in Beijing during the 2018-2019 heating season, accompanied by a decoupling analysis of the key influencing factors on performance. The observed seasonal coefficient of system performance (SCOP) ranged from 1.54 to 2.95, with an average of 2.21. Based on this large sample, three key influencing factors were identified, namely: terminal type, operating load rate and capacity regulation characteristics. In terms of terminal type, floor heating systems obtained a relatively high SCOP of 2.37 on average, due to the lower water temperature, compared with a radiator system average of 2.10. As for load rate, oversized capacity is a common problem: the recorded average annual operating load rate was only around 0.48, which resulted in high energy consumption from frequent on-off losses, and also increased power consumption by the circulating pump. This analysis provides engineering reference and support for the design and technological improvement of ASHP systems.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据