A new approach of DGA interpretation technique for transformer fault diagnosis

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijepes.2016.02.018

关键词

Power transformer faults; Dissolved gas analysis; Probability distribution function

向作者/读者索取更多资源

Dissolved Gas Analysis (DGA) is one of the most common techniques to detect the incipient faults in the oil -filled power transformers. In this paper, a new approach of DGA technique is proposed to overcome the conflict that takes place in the traditional interpretation techniques for transformer fault diagnosis. The new approach is based on the analysis of 386 dissolved gas samples data set that collected from the Egyptian electric utility chemical laboratory as well as from credited literatures. These data sets are used to build the technique model and also as a tested data set to get the technique's accuracy. The new approach DGA diagnoses the transformer fault types based on the gas concentration percentage limit of the sum of main five gases (Hydrogen (H-2), Methane (CH4), Ethan (C2H6), Ethylene (C2H4), and Acetylene (C2H2)) and some suggested gases ratios depending on the sample data set analysis. The validation of the proposed approach of DGA technique is satisfied by comparing its results with the results of the IEC Standard Code, Duval triangle and Rogers methods for the collected data set. The results refer to the ability and reliability of the new approach in transformer faults diagnostic. (C) 2016 Elsevier Ltd. All rights reserved.