MDPI
DOI: 10.3390/w14040663
关键词
building water quality management; opportunistic premise plumbing pathogens (OPPPs); Legionella spp; temperature control; COVID-19; recirculation loop; thermostatic mixing valve (TMV)
资金
- U.S. Environmental Protection Agency [R836880]
- EPA [R836880, 1100049] Funding Source: Federal RePORTER
This study assessed water quality management practices in large buildings in the United States and found that many buildings have issues with controlling Legionella spp. risks. There are also deficiencies in monitoring hot water temperatures, recirculation loop temperatures, showerhead replacement and disinfection, and overall water quality management.
Managing building water systems is complicated by the need to maintain hot water temperatures high enough to control the growth of Legionella spp. while minimizing the risk of scalding. This study assessed water quality management practices in large buildings in the United States. Surveys conducted with building water quality managers found that more than 85% of buildings have hot water temperatures that are consistent with scald risk mitigation guidelines (i.e., <122 degrees F/50 degrees C). However, nearly two thirds and three quarters of buildings do not comply with the common temperature guidance for opportunistic pathogen control, i.e., water heater setpoint > 140 degrees F (60 degrees C) and recirculation loop > 122 degrees F (50 degrees C), respectively; median values for both setpoint and recirculation loop temperatures are 10 degrees F (6 degrees C) or more below temperatures recommended for opportunistic pathogen control. These observations suggest that many buildings are prone to Legionella spp. risk. The study also found that 27% of buildings do not comply with guidelines for time to equilibrium hot water temperature, over 33% fail to monitor temperature in the recirculation loop, more than 70% fail to replace or disinfect showerheads, more than 40% lack a written management plan, and only a minority conduct any monitoring of residual disinfectant levels or microbiological quality. Given the rise in Legionellosis infections in recent years, coupled with highlighted water quality concerns because of prolonged water stagnation in plumbing, such as in buildings closed due to COVID-19, current management practices, which appear to be focused on scald risk, may need to be broadened to include greater attention to control of opportunistic pathogens. To accomplish this, there is a need for formal training and resources for facility managers.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐
暂无数据