Energy, exergy, and environmental (3E) analysis of a compound ejector-heat pump with low GWP refrigerants for simultaneous data center cooling and district heating

期刊

INTERNATIONAL JOURNAL OF REFRIGERATION
卷 133, 期 -, 页码 61-72

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2021.09.036

关键词

Low GWP refrigerants; Data center cooling; Photovoltaic thermal (PV/T); 3E assessment; Compound ejector-vapor compression; R134a alternatives

资金

  1. Southern Technical University in Iraq
  2. Spanish State Research Agency [IJC2019-038997-I]

向作者/读者索取更多资源

This study evaluated a novel compound PV/T waste heat driven ejector-heat pump system for data center cooling and waste heat recovery. Results showed remarkable overall performance enhancement for all investigated refrigerants, with R515B exhibiting the most pronounced improvement.
This work presents an energy, exergy, and environmental evaluation of a novel compound PV/T (photovoltaic thermal) waste heat driven ejector-heat pump system for simultaneous data center cooling and waste heat recovery for district heating networks. The system uses PV/T waste heat with an evaporative-condenser as a driving force for an ejector while exploiting the generated electric power to operate the heat pump compressor and pumps. The vapor compression system assessed several environmentally friendly strategies. The study compares eleven lower global warming potential (GWP) refrigerants from different ASHRAE safety groups (R450A, R513A, R515A, R515B, R516A, R152a, R444A, R1234ze(E), R1234yf, R290, and R1243zf) with the hydrofluorocarbon (HFC) R134a. The results prove that the system presents a remarkable overall performance enhancement for all investigated refrigerants in both modes. Regarding the energy analysis, the cooling coefficient of performance (COPC) enhancement ranges from 15% to 54% compared with a traditional R134a heat pump. The most pronounced COPC enhancement is caused by R515B (a 54% COPC enhancement and 49% heating COP enhancement), followed by R515A and R1234ze(E). Concerning the exergy analysis, R515B shows the lowest exergy destruction, with the highest exergy efficiency than all investigated refrigerants.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据