4.5 Article

Investigation on the efficiency degradation characterization of low ambient temperature air source heat pump under partial load operation

期刊

INTERNATIONAL JOURNAL OF REFRIGERATION
卷 133, 期 -, 页码 99-110

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2021.10.002

关键词

Low ambient temperature air source heat pump; Start-up loss; Stand-by loss efficiency degradation; Partial load factor

资金

  1. National Key RD Plan of China [2019YFE0103000]
  2. Science and Technology Project of the Ministry of Housing and Urban-Rural Development of People's Republic of China [2021-K-161]
  3. Tasks of Chinese Association of Refrigeration [KT201903]

向作者/读者索取更多资源

This study analyzed the mechanism of partial load efficiency degradation and proposed a new method for characterizing the partial load factor. Experimental tests were conducted on low ambient temperature ASHPs with different configurations to verify the accuracy of the new method.
The heating capacity of air source heat pump increases with the increase of ambient temperature, coupled with the heating demand decreases, resulting in a prolonged partial load operation. The partial load operation of low ambient temperature air source heat pumps applied in cold region is particularly serious. With that also comes an efficiency degradation, taking into consideration that the characterization method of current product standards is not uniform in different countries. In this paper, the mechanism of partial load efficiency degradation was analyzed firstly, the explicit relationship between cycling losses and cyclic time was derived, and a partial load factor characterization method of air source heat pump by coupling start-up loss and stand-by loss was proposed. Secondly, the cycling losses of 3 sets of low ambient temperature ASHPs with different configurations were tested under different ambient conditions by using the intermittent ON-OFF cycles tests method. The magnitude of start-up loss is 2.0%similar to 17.3% for test ASHPs, and the stand-by loss rises sharply from 4.2 to 8.9% for the test ASHPs as the PLR drops from 0.2 to 0.1. The accuracy of the PLF characterization method was verified, and especially that of the load rate below 0.2 was improved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据