4.6 Article

A Novel Traveling-Wave-Based Main Protection Scheme for ±800 kV UHVDC Bipolar Transmission Lines

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 31, 期 5, 页码 2159-2168

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2016.2571438

关键词

Faulty line selection; high resistance fault; line main protection; time domain; traveling wave; UHVDC system

资金

  1. National Natural Science Foundation Committee of China [51277143]

向作者/读者索取更多资源

The UHVDC transmission system has been increasingly used because of the advantages in long distance and large capacity transmission. However, the existing traveling-wave-based protection for UHVDC transmission lines is not sensitive enough to properly detect the internal fault with high fault resistance. A novel traveling-wave-based protection scheme for bipolar UHVDC lines is proposed in this paper. The discriminative characteristic between the internal and external fault, embodied in the backward traveling wave, is extracted to formulate the main protection criterion. The faulty line is identified by the polarity of the voltage fault component. In addition, only the single-pole voltage and current of rectifier side are required for the proposed protection scheme. The simulation and field data tests show that the proposed protection scheme can make a correct identification of the fault section and selection of the faulty line in the +/- 800 kV UHVDC system and +/- 500 kV HVDCsystem. Besides, the proposed protection can correctly detect the grounding fault with fault resistance up to 500 Omega.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据