期刊
IEEE TRANSACTIONS ON POWER DELIVERY
卷 31, 期 4, 页码 1437-1446出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2016.2520928
关键词
Commutation failure; control mode ambiguity; extinction angle; high-voltage direct-current (HVDC) system; overlap angle; phase shift
资金
- Incheon National University Research Grant
High-voltage direct-current (HVDC) systems are being widely employed in various applications owing to their advantages, such as bulk power transmission, long-distance transmission, and power-flow control. However, HVDC systems suffer from-commutation failure, a major drawback that leads to increased device stress, interruptions in transmitted power, and problems related to protection relay setting, in turn, resulting in system instability during operation. Therefore, many studies have investigated the mitigation of commutation failure by considering its underlying factors, that is, ac voltage reduction, dc current increment, and crossing point shifts of phase voltage. However, these approaches are limited in that they are unable tomitigate intermittent commutation failure in a transient state. This study proposes an improved algorithm that mitigates commutation failure by considering the results of previous studies as well as the control characteristics of HVDC systems. The proposed algorithm is tested in various scenarios, and the test results verify its feasibility.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐