4.6 Article

An Algorithm for Effective Mitigation of Commutation Failure in High-Voltage Direct-Current Systems

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 31, 期 4, 页码 1437-1446

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2016.2520928

关键词

Commutation failure; control mode ambiguity; extinction angle; high-voltage direct-current (HVDC) system; overlap angle; phase shift

资金

  1. Incheon National University Research Grant

向作者/读者索取更多资源

High-voltage direct-current (HVDC) systems are being widely employed in various applications owing to their advantages, such as bulk power transmission, long-distance transmission, and power-flow control. However, HVDC systems suffer from-commutation failure, a major drawback that leads to increased device stress, interruptions in transmitted power, and problems related to protection relay setting, in turn, resulting in system instability during operation. Therefore, many studies have investigated the mitigation of commutation failure by considering its underlying factors, that is, ac voltage reduction, dc current increment, and crossing point shifts of phase voltage. However, these approaches are limited in that they are unable tomitigate intermittent commutation failure in a transient state. This study proposes an improved algorithm that mitigates commutation failure by considering the results of previous studies as well as the control characteristics of HVDC systems. The proposed algorithm is tested in various scenarios, and the test results verify its feasibility.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据