4.6 Article

Efficient and Low-Cost PD Monitoring and Locating System for MV Switchgears Using TEV Detectors

期刊

IEEE TRANSACTIONS ON POWER DELIVERY
卷 36, 期 5, 页码 3266-3269

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2021.3089030

关键词

Partial discharge; MV switchgears; transient earth voltage; location; modularization

资金

  1. Shaanxi Electric Power Research Institute of State Grid in China [PESL-00077-2021]

向作者/读者索取更多资源

This paper presents a PD monitoring and locating system for medium-voltage switchgears using transient earth voltage (TEV) detectors. The system utilizes a time-of-flight methodology to identify the switchgear affected by PD among a row of switchgears, and implements a time sharing access mechanism to automatically identify the site of PD. Experimental results confirm the efficiency of the system in identifying switchgear with PD among three 10 kV metal-clad switchgears.
Identifying the location of partial discharges (PDs) and providing clear information on insulation vulnerabilities in power systems can help utility companies to improve their maintenance efficiency. This paper presents a PD monitoring and locating system for medium-voltage switchgears using a set of transient earth voltage (TEV) detectors. A time-of-flight methodology was used to identify the switchgear affected by PD among a row of switchgears. A time sharing access mechanism, which was implemented by multiple high-frequency surface mounting relays integrated into each TEV detector, was applied to automatically identify the site of PD and minimize the number of expensive high-speed acquisition cards. The operation principle and implementation of the modular system were formulated, and the efficiency of the proposed system in identifying the switchgear with PD among three 10 kV metal-clad switchgears was confirmed experimentally.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据