4.7 Article

Experimental study and multi-objective optimisation of a novel integral thermoelectric wall

期刊

ENERGY AND BUILDINGS
卷 252, 期 -, 页码 -

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2021.111403

关键词

Integral thermoelectric wall; Cooling performance; Heating performance; NSGA-II; Multi-objective optimisation

资金

  1. Fundamental Research Funds for the Central Universities, China [531118010427]
  2. National Natural Science Foundation of China [52078198]

向作者/读者索取更多资源

This study introduces a simple and practical integral thermoelectric wall (ITEW) that eliminates heat losses or gains of the wall and provides indoor cooling and heating capacity. By optimizing key parameters, the cooling and heating performance of ITEW can be simultaneously improved.
The development of a high-performance building envelope is critical to the improvement of building energy efficiency. As the building-integrated thermoelectric envelope (BITE) has a complex structure, development of a simple and practical thermoelectric wall is relevant. Therefore, this study proposes an integral thermoelectric wall (ITEW) with a simple structure that can easily be integrated into a building wall. The ITEW not only eliminates the heat losses or gains of the wall but also provides indoor cooling and heating capacity. A theoretical model of the ITEW was first established and verified using detailed experiments. To realise the highest performance of the ITEW, the optimal ranges of five key parameters- the direct current, number of PN couples, thermoelectric element leg length, thermoelectric element cross-sectional area, and heat dissipation condition-were determined. Thereafter, taking these value ranges as constraints, the Non-dominated Sorting Genetic Algorithm-II was used to perform a multi objective optimisation in summer and winter conditions. The results show that the cooling and heating performances of the ITEW can be simultaneously improved. The cooling coefficient of performance ranged from 2 to 7, and the cooling capacity per unit area ranged from 2 to 70 W/m(2). Meanwhile, the heating coefficient of performance ranged from 1 to 8 and reached values greater than 4 under conventional building heat load demand. The results of this study, therefore, establish a foundation for the development and application of the ITEW system. (C) 2021 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据