4.5 Article

Real Time Sustainable Power Quality Analysis of Non-Linear Load under Symmetrical Conditions

期刊

ENERGIES
卷 15, 期 1, 页码 -

出版社

MDPI
DOI: 10.3390/en15010057

关键词

power quality; voltage sag; induction motor; grid emulator; ANSYS

向作者/读者索取更多资源

This paper analyzes the impact of voltage sag on induction motors and considers different types of voltage sags in the experiment. The results aid in the design of more accurate induction motors and provide a proposed modification to further study the performance of induction motors during voltage sag events.
Voltage sag is one of the most significant power quality problems in the industry and has a significant impact on induction motor safety and stability. This paper analyzes the characteristics of voltage dips in power systems and induction motors with a special emphasis on balanced dips with the help of virtual grids (regenerative grid simulator), as per IEC 61000-4-11. Three phase induction motors with 3.3 kW, 16 A coupled to a DC generator with 3.7 kW, and 7.8 A rated are considered for the test analysis. This paper aids in the development of an induction motor to achieve improved precision by taking different voltage sags into account. The experimental results benefit the design modifications of induction motors at industrial and other commercial levels of consumers regarding major power quality issues and the behavior of the induction motors. A proposed modification employing ANSYS is provided to further examine the precise performance of induction motors during sag events.