4.6 Article

A novel technique for condition monitoring of metal oxide surge arrester based on fifth harmonic resistive current

期刊

ELECTRIC POWER SYSTEMS RESEARCH
卷 202, 期 -, 页码 -

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.epsr.2021.107576

关键词

Metal oxide surge arresters; Condition monitoring; Leakage current; Third harmonic resistive current; Fifth harmonic resistive current; Total Harmonic Distortion (THD)

资金

  1. Universiti Teknologi Malaysia [4B482, 01M44, 02M18, 05G88]
  2. Higher Education Commission Pakistan (HRDI)

向作者/读者索取更多资源

This study introduces the fifth harmonic of resistive current (I-R5th) as a new ageing indicator for metal oxide surge arresters (MOSA), showing similar sensitivity towards ageing as compared to the third harmonic current. Additionally, it has been found that the variation in I-R5th with the fifth harmonic voltage is smaller than the variation in I-R3rd with the third harmonic voltage.
The ageing in metal oxide surge arresters (MOSAs) is monitored by measuring their leakage current parameters. Particularly, the third harmonic component of resistive leakage current is directly correlated with the ageing and degradation of the arrester. However, the third harmonic of resistive current (I-R3rd) is also affected by the third harmonic component in the grid's voltage. Therefore, I-R3rd based monitoring may lead to an inaccurate condition assessment of MOSA when the supply voltage comprises third harmonic content. Hence, this paper introduces the fifth harmonic of resistive current (I-R5th) as a new ageing indicator for MOSA. This study has been done experimentally on five samples of aged polymeric MOSAs rated at 120kV. Results have shown that the IR5th exhibits similar sensitivity towards ageing as compared to the I-R3rd. Additionally, it has been found that the variation in I-R5th with the fifth harmonic voltage is smaller than the variation in I-R3rd with the third harmonic voltage. Therefore, the following technique can support the online condition monitoring of MOSAs in a more realistic way than the existing third harmonic current measurement technique.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据