4.5 Article

Self-Consistent Multi-arcs Dynamic Model for High Voltage Polluted Insulators

出版社

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TDEI.2016.7736851

关键词

Self-consistent multi-arcs dynamic model; high voltage polluted insulators; impulse voltage; flashover voltage; leakage current

向作者/读者索取更多资源

This paper presents a self-consistent multi-arcs dynamic model for high voltage polluted insulator under impulse voltage. This model is an improvement of that one developed for single arc; it is based on an electrical equivalent circuit consisting of a series of different partial arcs and residual layer resistance. It takes into account the configuration of insulator, applied voltage polarity and the instantaneous changes of discharges parameters. The proposed model enables to compute the flashover voltage and leakage current and to show the influence of dry bands on the voltage distribution along the surface and furthermore on the electrical performance of polluted insulator. It is validated using a simple plane model in the case of uniform and non-uniform polluted bands. The computed flashover voltage and leakage current are found in good agreement with those measured experimentally.