4.7 Article

Predictive modelling and optimization of HVAC systems using neural network and particle swarm optimization algorithm

期刊

BUILDING AND ENVIRONMENT
卷 209, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2021.108681

关键词

Predictive control; NARX; Indoor environment; Energy saving; HVAC operational setpoint

资金

  1. Murdoch University Research Studentship (MURS) Scholarship
  2. Murdoch University Energy Management Facility

向作者/读者索取更多资源

This study proposes an advanced modeling and optimization approach to minimize the energy consumption of HVAC systems without compromising indoor environmental quality. Real-time predictive models are developed using a nonlinear autoregressive exogenous neural network, and optimized to consider seasonal variations. The results indicate that it is possible to reduce total energy consumption while maintaining indoor environmental conditions within acceptable ranges.
The concept of maintaining indoor environmental quality comprising building indoor temperature, relative humidity, CO2, and volatile organic compound (VOC) level poses new challenges to the optimal operation of heating, ventilation and air-conditioning (HVAC) systems. While existing case studies demonstrate the energy saving potentials for efficient HVAC operation, there is a lack of studies quantifying energy savings whilst considering indoor environmental conditions. This study proposes a state-of-the-art modelling and optimization approach to minimize the energy consumption of the HVAC systems without compromising indoor environmental quality. While the primary objective of ensuring optimal operation of HVAC systems is to minimize energy consumption, controlling indoor environmental parameters to remain within the acceptable range imposes excess energy use. These two conflicting objectives constitute a multi-variable constrained optimization problem that has been solved using a particle swarm optimization (PSO) algorithm. Real-time predictive models are developed for the individual indoor environmental parameters and HVAC energy consumption using a Nonlinear Autoregressive Exogenous (NARX) neural network (NN). During model development, models' performance is optimized in terms of complexity, predictive accuracy, and ease of application to a real system. The proposed predictive models are then optimized to provide an optimal control setting for the HVAC systems considering seasonal variations. The results indicate that it is possible to reduce 7.8% of total energy, without negotiating indoor environmental conditions, e.g., air temperature 19.60-28.20C and relative humidity 30-65% as per ASHRAE Standard 55, and CO2 <= 800 ppm and VOC <= 1000 ppm as per AS 1668.2.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据