Effects of operating room layout and ventilation system on ultrafine particle transport and deposition

期刊

ATMOSPHERIC ENVIRONMENT
卷 270, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.atmosenv.2021.118901

关键词

Air quality; Computational Fluid Dynamic (CFD); Particle deposition; Particle transport; Operating rooms; Ultrafine particles

向作者/读者索取更多资源

The study aims to analyze the effectiveness of three different ventilation systems in controlling UFP transport and deposition in operating rooms. The results show that both laminar airflow and turbulent mixing airflow systems can effectively remove UFPs and ensure a low particle deposition rate compared to the evacuation rate. In addition, the choice of instrument table position also affects the deposition of UFPs, CFUs, and contaminants, and the UFP concentration at the height of the surgical staff's head cannot be neglected for health-related risks.
The main role of Heat Ventilation and Air Conditioning (HVAC) systems in Operating Rooms (ORs) is to ensure the desired thermo-hygrometric conditions and indoor air quality, minimizing the risk of air contamination. The main sources of contamination inside ORs, during surgical operations, are Colony-Forming Units (CFUs), fine particles and ultrafine particles (UFPs), which could cause surgical site infections or health issues for the medical staff. The present work aims at increasing the scientific knowledge concerning numerical modelling of the UFP transport and deposition in ORs, analysing the effectiveness of three different ventilation systems. A numerical methodology, validated in previous works, has been used to study UFP transport and deposition inside three actual ORs, two of them equipped with a Laminar AirFlow (LAF) system and one with a Turbulent Mixing Airflow (TMA) system. Both the LAF and the TMA systems effectively evacuate the UFPs, ensuring a particle deposition rate significantly lower than the evacuation rate. The installation of extraction grilles near the surgical table allows obtaining an improvement of UFP evacuation. Due to the not perfect symmetry of OR layouts and surgical wound position, a preferred way for UFP transport can be observed. The instrument table position should be chosen consequently, to reduce UFP, CFU and contaminant deposition. The UFP concentrations at surgical staff head height cannot be neglected for health-related risks.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据