Frosting in heat pump evaporators part A: Experimental investigation

期刊

APPLIED THERMAL ENGINEERING
卷 199, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2021.117487

关键词

Heat pump; Evaporator; Frost growth; Heat transfer

资金

  1. Austrian Research Promotion Agency (FFG)
  2. Austrian Climate and Energy Fund (KLIEN) [848891]
  3. European Commission within the 7th Framework Programme (FP7) [FP7-Energy-2012-308816]

向作者/读者索取更多资源

This study analyzed the frost growth on the evaporator of a 5 kW air-to-water heat pump assembly and found that treating the evaporator surfaces with a hydrophobic nano-coating can reduce the frost growth rate and increase the time intervals between defrosting..adjusted, Furthermore, the coated evaporator showed a reversed behavior when the air inlet temperature was below freezing point compared to the uncoated evaporator in terms of defrosting intervals.
Frost growth on an evaporator of a 5 kW air-to-water heat pump assembly was analysed using several experimental approaches. For comparative testing, the evaporators fin and tube surfaces were treated with a hydrophobic nano-coating and the difference in frosting was investigated. Besides thermodynamic measurement data, transient frost mass and extracted frost layer thickness was available through the use of a scale and image capturing techniques, respectively. Images using a thermographic-, a macro- and overview-cameras were analysed for several climatic conditions established in a climate chamber. Time intervals between defrosting at +4.5 degrees C ambient temperature increased significantly by around 20% for the coated evaporator compared to the uncoated evaporator. This difference, however, got reduced when lowering the air inlet temperature below the freezing point, where this behaviour got reversed and the coated evaporator needed shorter intervals between defrosting compared to the uncoated one. This trend is also supported by the extracted frost thicknesses from the macro-camera image stream and by analysing the transient brightness signal of full evaporator image streams characterized in this work. Frost mass growth rate is reduced between 16% and 26% for -2.0 degrees C to +5.5 degrees C ambient temperature, respectively for the coated evaporator compared to the mass growth rate of the uncoated one. Parametric studies of evaporator frosting of this 5kW air-source heat pump at multiple air inlet stream conditions build up the base for comparison to the numerical work presented in Part B of this publication.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据