Numerical Study on Flow Heat Transfer Characteristics of Horizontal Tube Falling-Film Evaporator

期刊

JOURNAL OF THERMAL SCIENCE
卷 30, 期 4, 页码 1302-1317

出版社

SPRINGER
DOI: 10.1007/s11630-021-1478-4

关键词

horizontal single tube; evaporator; falling film; numerical simulation; heat transfer

资金

  1. National Natural Science Foundation of China [52006031]
  2. international cooperation project of China Manned Space Program [6903001173]

向作者/读者索取更多资源

The application of horizontal tube falling film evaporation in horizontal single tube and evaporator shows that spray density and temperature have an impact on the total heat transfer coefficient, liquid film thickness varies with tube diameter, and the total heat transfer coefficient increases with the increase in liquid distribution height and density.
As an efficient and energy-saving heat exchange technology, horizontal tube falling film evaporation has a great application prospect in refrigeration and air conditioning. The three-dimensional models of falling film flow evaporation outside horizontal single tube and inside evaporator were established, and the accuracy of flow and heat transfer simulation process was verified by comparison. For horizontal single tube, the results showed that total heat transfer coefficient was low and increased with larger spray density and evaporation temperature. The thickness of liquid film outside tube decreased gradually with the increase of tube diameter, and the total heat transfer coefficient of small tube diameter was significantly greater than that of the large tube diameter. The total heat transfer coefficient presented an increasing trend with larger liquid distribution height and density. In addition, the fluctuation of tube axial liquid film thickness distribution decreased with larger liquid distribution density. For evaporator, the results indicated that part of liquid refrigerant was carried into the vapor outlet. The temperature of tube wall and fluid presented a gradually rising trend in vertical downward direction, while tube wall temperature within the same horizontal and transverse row had little difference. The high-temperature zone on the outer wall of heat exchange tube moved towards the inlet and gradually decreased, and the outlet temperature of water in the tube also gradually decreased with the increase of refrigerant spray density. The local heat transfer coefficient of heat exchanger tube in the vertical direction presented a downward trend which was more obvious with the smaller spray density and it was obviously higher located in the middle of upper tube row and both sides of lower tube row for horizontal tube rows.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据