4.7 Article

Economic optimization of auxiliary heat source for centralized solar district heating system in Tibetan Plateau, China

期刊

ENERGY CONVERSION AND MANAGEMENT
卷 243, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.enconman.2021.114385

关键词

Auxiliary heat source; Centralized solar district heating system; Economic analysis; Levelized cost of heat; Solar fraction

资金

  1. National Natural Science Foundation of China [52078408]
  2. State Key Program of National Natural Science Foundation of China
  3. Science Foundation for Outstanding Youth of Shaanxi Province
  4. Special fund for guiding Local Science and Technology Development by the Central Government of China [2019ZY-FP-06]

向作者/读者索取更多资源

The study found that the electric boiler is suitable for areas with abundant solar irradiation, with a required SF of over 85%, while the air source heat pump is better for areas with poor solar irradiation and a SF below 50%. Maintenance cost changes significantly affect the LCOH, with a greater impact when the SF is higher. Increasing the non-guaranteed rate for the air source heat pump can improve the overall economy of the system.
For a centralized solar district heating system (CSDHS), an appropriate auxiliary heat source (AHS) is essential to improve the financial benefits. In order to find an economical AHS for the CSDHS in Tibetan Plateau, China, four typical cities (Nyingchi, Qamdo, Lhasa, and Shigatse) and three most commonly used AHSs (electric boiler, gas boiler and air source heat pump) are selected as the research objects in the current work. The levelized cost of heat (LCOH) is taken as the main evaluation index, and the software package, TRNSYS, is used to simulate and analyze the performance of the system. The selection of AHS and the corresponding solar fraction (SF) of the CSDHS are optimized. The results show that the electric boiler is suitable for areas with abundant solar irradiation, where the SF should be greater than 85%. The air source heat pump is found to be suitable for areas with ordinary or poor solar irradiation, where the SF is less than 50%. The change in maintenance cost has a significant influence on LCOH. Moreover, the higher the SF, the greater is the influence of maintenance cost on LCOH. In addition, when the air source heat pump is used for AHS, the non-guaranteed rate can be appropriately increased, which improves the overall economy of the system. The results can be used to effectively optimize the economic performance of a CSDHS, and provide reference for the design of an AHS and SF in different areas of the Tibetan Plateau, China.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据