4.7 Article

Evaluation of different personalized ventilation air terminal devices: Inhalation vs. clothing-mediated exposures

期刊

BUILDING AND ENVIRONMENT
卷 192, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2021.107637

关键词

Personalized ventilation; Clothing contamination; Inhalation intake fraction; Deposition fraction; Computational fluid dynamics

资金

  1. American University of Beirut (AUB)
  2. National Council for Scientific Research of Lebanon (CNRS-L)
  3. ASPIRE Zone Foundation, Doha, Qatar [QUEX-CENG-ASPIRE-11/12-7]

向作者/读者索取更多资源

The study investigated the impact of personalized ventilation systems on reducing inhalation exposure to indoor particles and clothing contamination by particle deposition. Results demonstrated that different ventilation devices at varying flow rates had different effects on exposure and deposition.
Human exposure to particles indoors occurs through direct inhalation or indirectly through deposition on clothes that release them in other spaces. Ventilation systems are installed to decrease direct exposure but little is known about their effect on clothing-mediated exposures. This work weighs the effect of personalized ventilation (PV) systems on decreasing inhalation exposure to indoor particles versus their contribution to clothing contamination by particle deposition. To conduct this work, a 3D computational fluid dynamics model was developed for an office conditioned by mixing ventilation and common PV air terminal devices: computer mounted panel (CMP), vertical desk grill (VDG) and round movable panel (RMP). Typical particle sources were considered: furniture resuspension and human breathing. The model was validated experimentally in a climatic chamber by comparing real-time particle mass concentration near a thermal manikin. Results showed that CMP delivering 5 l/s reduced total inhalation exposure by 27% and deposition by 72% compared to standalone mixing ventilation. Increasing the flow to 10 l/s led to reductions of 89% in exposure and 56.5% in deposition. A VDG delivering 5 l/s reduced exposure by 33% while deposition reduction was negligible at 3%. Increasing the flow rate to 10 l/s reduced exposure by 91% and slightly increased deposition by 12%. The RMP at 5 l/s and 10 l/s reduced exposure by 89% and 97% respectively and increased deposition by 70% and 80% respectively. Among the three ATDs, the CMP offered the best compromise between reducing inhalation exposure and clothing-mediated exposures at all possible flow rates.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据