4.6 Article

Experimental Study on Delaying the Failure Time of In-Service Cables in Trays by Using Fire-Retardant Coatings

期刊

APPLIED SCIENCES-BASEL
卷 11, 期 6, 页码 -

出版社

MDPI
DOI: 10.3390/app11062521

关键词

fire-retardant coatings; insulation failure; cable tray; ISO 834 fire scenario

资金

  1. Funds of Guangdong Provincial Key Laboratory of Fire Science and Technology [:39000-42080092]

向作者/读者索取更多资源

The proposed modification scheme of spraying fire-retardant coatings on the cable tray in an oil storage company has been shown to effectively improve the fire protection of key cables connected to firefighting and safety equipment. Experimental results indicate that the failure time of cables can be significantly delayed by using fire-retardant coatings, with thicker coatings having a better fireproof effect. Fire-retardant coatings were found to be more effective in fire protection than fire-resistant cotton.
Featured Application The scheme proposed in this paper will be applied to the fire protection of the cables in service in an oil storage company. Improving the fire resistance of the key cables connected to firefighting and safety equipment is of great importance. Based on the engineering practice of an oil storage company, this study proposes a modification scheme that entails spraying fire-retardant coatings on the outer surface of a cable tray to delay the failure times of the cables in the tray. To verify the effect, 12 specimens were processed using five kinds of fire-retardant coatings and two kinds of fire-resistant cotton to coat the cable tray. The specimens were installed in the vertical fire resistance test furnace. For the ISO 834 standard fire condition, a fire resistance test was carried out on the specimens. The data for the surface temperature and the insulation resistance of the cables in trays were collected, and the fireproof effect was analyzed. The results showed that compared with the control group, the failure time of the cable could be delayed by 1.57-14.86 times, and the thicker the fire-retardant coatings were, the better the fireproof effect was. In general, the fire protection effect of the fire-retardant coating was better than that of the fire-resistant cotton.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据