4.7 Article

Operating energy savings in a liquid desiccant and dew point evaporative cooling-assisted 100% outdoor air system

期刊

ENERGY AND BUILDINGS
卷 116, 期 -, 页码 535-552

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2016.02.011

关键词

Non-vapor-compression system; Liquid desiccant; Dew point evaporative cooling; 100% outdoor air system; Energy simulation

资金

  1. National Research Foundation (NRF) grant - Korean government [2015R1A2A1A05001726]
  2. National Research Foundation of Korea [2015R1A2A1A05001726] Funding Source: Korea Institute of Science & Technology Information (KISTI), National Science & Technology Information Service (NTIS)

向作者/读者索取更多资源

The main purpose of this study is to develop a liquid desiccant and dew point evaporative cooling assisted 100% outdoor air system (LDEOS), and to evaluate its energy saving potentials. In recent years, non-vapor-compression air conditioning systems are becoming available without compromising energy efficiency, thermal comfort, and ventilation requirements. A quasi-dynamic simulation model of LDEOS including a dew point evaporative cooler model was developed to compare the energy performance of LDEOS against a typical variable air volume (VAV) system. A sequence of operation for LDEOS was also proposed. Simulation results showed that LDEOS could save 12% of primary energy compared to a conventional VAV, while 100% of outdoor air was conditioned and delivered to the space without using vapor compression technology. (C) 2016 Elsevier B.V. All rights reserved.