4.7 Article

Impact of ASHRAE's museum climate classes on energy consumption and indoor climate fluctuations: Full-scale measurements in museum Hermitage Amsterdam

期刊

ENERGY AND BUILDINGS
卷 130, 期 -, 页码 286-294

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.enbuild.2016.08.016

关键词

Energy; Saving; Museum; Historical building; Ashrae

向作者/读者索取更多资源

In the 20th century, museum indoor climates have been conditioned ever more strictly, sometimes beyond guidelines, allowing no fluctuations at all. Among other effects, this has led to excessive energy demands. At the start of the 21st century, interest has increased to condition the indoor climate more reasonable. This study assessed the energy impact of three levels of museum climate control: Reference (21 degrees C/50% RH, no permissible fluctuations), ASHRAE's Class AA, ASHRAE's Class A. Full-scale measurements were conducted in the museum Hermitage Amsterdam for one year. The results show that Class AA saved 49% and Class A saved 63% compared to the Reference setpoint strategy. Moreover, relaxing the climate specifications decreased hourly fluctuations, but increased daily fluctuations. It is highly likely that the overall degradation risk has not significantly changed for most artefacts. (C) 2016 Elsevier B.V. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据