4.6 Article

OLTC transformer model connecting 3-wire MV with 4-wire multigrounded LV networks

期刊

ELECTRIC POWER SYSTEMS RESEARCH
卷 192, 期 -, 页码 -

出版社

ELSEVIER SCIENCE SA
DOI: 10.1016/j.epsr.2020.107003

关键词

ZBUS power flow; Multi-grounded networks; OLTC transformer

资金

  1. European Union (European Social Fund-ESF) through the Operational Programme Human Resources Development, Education and Lifelong Learning [MIS-5000432]

向作者/读者索取更多资源

This paper presents a comprehensive model of on-load tap-changer (OLTC) transformers that connects a 3-wire medium voltage (MV) network with a 4-wire multigrounded low voltage (LV) network. The proposed model has been validated in a 4-Bus network and its performance tested in the IEEE 8500-Node and IEEE 906-Bus test networks. The model allows for the inclusion of both MV and LV networks in a single YBUS matrix without the need for refactoring during tap changes.
This short communication presents a comprehensive model of on-load tap-changer (OLTC) transformers that connects 3-wire medium voltage (MV) with 4-wire multigrounded low voltage (LV) networks. The proposed model enables the inclusion of the 3-wire MV network and the 4-wire multigrounded LV network into a single YBUS matrix without any assumption or simplification. Its distinct feature is that the tap changer of the transformer is simulated outside the YBUS matrix, thus a refactorization of the YBUS matrix is not required in every tap change. The proposed transformer model has been validated in a 4-Bus network, while its performance has been tested in the IEEE 8500-Node and IEEE 906-Bus test networks.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。