Impact of emergency diesel generator reliability on microgrids and building-tied systems

期刊

APPLIED ENERGY
卷 285, 期 -, 页码 -

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.apenergy.2021.116437

关键词

Emergency diesel generators; Microgrids; Reliability; Energy resilience; Microgrid reliability; Generator reliability

资金

  1. U.S. Department of Energy (DOE) [DE-AC36-08GO28308]
  2. Department of Defense's Environmental Security Technology Certification Program (ESTCP) [IAG-18-02080]

向作者/读者索取更多资源

The traditional emergency diesel generator systems tied to individual buildings, even with multiple generators per building, cannot meet the critical load requirements for extended grid outages lasting multiple days. In contrast, diesel generator-based microgrid configurations offer higher reliability and can better support longer duration power outages.
Microgrids are an emerging alternative as an energy backup system for critical electric loads and have improved performance compared to the traditional architecture where a single emergency diesel generator is tied to an individual building. Both architectures are dependent on the reliability of their individual generators and a quantitative and realistic comparison of the overall system reliability of the two architectures is lacking. Using recently published work on emergency diesel generator finite reliability, a quantitative methodology is presented to compare the reliability of a microgrid architecture based on centralized emergency diesel generators to the traditional approach of generators tied to individual buildings. Three system reliability performance metrics are calculated as a function of outage duration: (1) probability to meet 100% of the critical load; (2) expected fraction of lost load; and (3) probability to meet the highest priority critical loads. It is shown that stand-alone building-tied emergency diesel generators systems, even when two emergency diesel generators are used per building, cannot provide the reliability required to sustain critical loads for a grid outage lasting multiple days. Due to their network configuration and ability to share load, diesel generator-based microgrid configurations are estimated to have > 93% probability of powering all buildings for a 2-week outage there the individual building tied emergency diesel generator architecture has a <= 20% probability. Microgrids do present other susceptibilities that are site specific and should be considered including vulnerabilities associated with the on-campus distribution system and cybersecurity.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据