期刊
IEEE TRANSACTIONS ON POWER SYSTEMS
卷 36, 期 1, 页码 557-560出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRS.2020.3029418
关键词
Area control error; automatic generation control; load-frequency control; secondary frequency control
资金
- NSERC [RGPIN-2017-04008]
This study reexamines and criticizes the classical area control error concept in automatic generation control, proposing a new error signal called the area injection error that improves AGC performance by directly measuring generator power levels. The analysis concludes that effective frequency biasing in a common textbook implementation of AGC is larger than intended, leading to unintended interaction between control areas. Simulations on a detailed two-area test system validated the proposed theory.
We reexamine and critique the classical area control error concept used in automatic generation control, and propose a new error signal termed the area injection error. Unlike the ACE, the AIE uses direct measurement of generator power levels, yielding improved AGC performance in the presence of bias uncertainty and nonlinearity in generator turbine-governor responses. As a by-product of our analysis, we conclude that the effective frequency biasing found in a common textbook implementation of AGC is larger than intended, resulting in unintended interaction between control areas. Our theory is validated via simulations on a detailed two-area test system.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐
暂无数据