Experiments and numerical simulation on the suppression of explosion of propane/air mixture by water mist

期刊

COMBUSTION AND FLAME
卷 223, 期 -, 页码 192-201

出版社

ELSEVIER SCIENCE INC
DOI: 10.1016/j.combustflame.2020.09.014

关键词

Water mist; Minimum ignition energy; Ignition probability; Suppression effectiveness; CHEMKIN

资金

  1. JSPS [JP26282098]

向作者/读者索取更多资源

Experiments and numerical simulations were conducted to investigate the impact of water mist on the minimum ignition energy and flammability limits of C3H8-air mixtures. Results showed that water mist can increase the minimum ignition energy density, but its suppression effectiveness depends on the equivalence ratio and mass fraction of water mist. The smaller the diameter of the water mist, the greater the suppression potential.
Effect of water mist on minimum ignition energy (MIE) and lower and upper flammability limits (LFL and UFL) of C3H8-air mixtures were investigated by experiments and numerical simulation. Ignition experiments were performed in a combustion tube. Polydisperse water mist with a Sauter mean diameter of D-32 = 21 mu m was generated by a piezoelectric atomizer. Mixture was ignited by an exploding wire heated instantaneously by electrical discharge. Ignition probability follows the cumulative probability distribution function of energy density, i.e., energy per unit volume of the wire. Water mist increases minimum ignition energy density (MIED) defined at 50% ignition probability when the equivalence ratio 9 1.0 and 9 1.3. However, for 1.0 < 9 < 1.3, the suppression effectiveness was scarcely observed. In numerical simulation, water mist was assumed to be an imaginary ideal gas and evaporation process was expressed by a chemical reaction. Ignition energy is added in the flame kernel at the center and the flame propagates spherically if ignited. This model can predict MIE of the mixture without water mist reasonably. MIE increases nonlinearly with the mass fraction of water mist Y-0 and flammability range narrows. At Y-0 = 0.146 and beyond, the mixture of any 9 becomes unable to be ignited. Relative suppression effectiveness factors Se and Ss are newly introduced for experiments and simulation, respectively. Comparison of Se with Ss shows that the water mist is not so effective as expected by simulation. The life time of a droplet before evaporation is much longer for the water mist of D-32 = 21 mu m than the residence time in the flame, and only a part of water mist can evaporate in the flame zone. To make full use of the suppression potential of water mist, the mist diameter should be sub-5 mu m. (C) 2020 The Combustion Institute. Published by Elsevier Inc. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据