4.7 Article

Performance of an internally cooled and heated desiccant-coated heat and mass exchanger: Effectiveness criteria and design methodology

期刊

APPLIED THERMAL ENGINEERING
卷 188, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2021.116593

关键词

Desiccant dehumidification; Air conditioning; HVAC; Desiccant coated heat exchanger; Modeling; Fin tube heat exchanger

资金

  1. National Research Foundation (NRF), Singapore
  2. EIRP (Energy Innovation Research Programme) [R-263-000-B82-279]

向作者/读者索取更多资源

This study introduces equations and calculation methods for internally cooled and heated desiccant-coated heat and mass exchangers (ICHDHMX) and demonstrates through simulations that ICHDHMX can operate efficiently at low regeneration temperatures, making it suitable for various conditions in warm and humid weather.
Internally cooled and heated desiccant-coated heat and mass exchangers (ICHDHMX) driven by low-grade heat are very attractive owing to their energy-saving potential, especially for applications where substantial moisture removal (such as air-conditioning) is a necessity. In this paper, we derive equations for the performance of an ideal ICHDHMX, allowing us to define humidity-ratio effectiveness (epsilon(Y)) and relative-humidity effectiveness (epsilon(RH)) such that their values approach 1 as the performance approaches that of an ideal ICHDHMX. Besides an equation-based approach, an easy-to-use psychrometric-chart based approach is presented to determine the performance of an ideal ICHDHMX. We invoke conservation principles to ascertain whether or not it is feasible to use the ICHDHMX for a given set of inlet conditions of air and water streams for dehumidification and regeneration. The dimensions of the ICHDHMX can be determined using this methodology, not even requiring knowledge of a tuning parameter unless a precise outlet specific humidity is required. Simulations are conducted for cases involving three incoming hot water temperatures (38, 44 and 50 degrees C) and several mixing ratios of room return air (25 degrees C at 0.011 kg/kg dry air) and outdoor air (32 degrees C at 0.02 kg/kg dry air), typical of warm and humid weather conditions. For all cases, the cool-water inlet is fixed at 30 degrees C. The results show that even when the dehumidification air-stream humidity is high, if the regeneration air-stream humidity is low (typical of room-exhaust air), the operation of an ICHDHMX is feasible using a low regeneration temperature of only 38 degrees C. When the regeneration temperature is 50 degrees C, the exchanger can operate under the complete range of humidity conditions tested. A cooling coefficient of performance up to 9.8 and effectiveness value up to 0.88 is realized, while the fluid power required is generally very low. These findings substantiate the case for commercial adoption of this technology for air-conditioning.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据