4.7 Article

Experimental study on a fresh air heat pump desiccant dehumidification system using rejected heat

期刊

APPLIED THERMAL ENGINEERING
卷 179, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2020.115742

关键词

Dehumidification; Desiccant coated heat exchanger (DCHE); Vapor compression heat pump; Isothermal

资金

  1. Natural Science Foundation of China [51961165110]

向作者/读者索取更多资源

Desiccant coated heat exchanger (DCHE) was proposed for highly efficient dehumidification process due to the adsorption heat could be eased by inner cooling during the sorption process. Meanwhile, heat pump is probably used with DCHE together in humidity control processes because cooling and heating generated by vapor compression heat pump system match with the energy demand of DCHE well. A fresh air heat pump desiccant dehumidification system using rejected heat with desiccant coated heat exchanger (DCHE) was set up and experimentally tested in this paper. Near isothermal dehumidification process could be realized due to the utilization of DCHE which could convert the sensible cooling provided by vapor compression heat pump subsystem to latent cooling to increase the moisture removal of the system. The optimal average moisture removal and COP are 7.02 g/kgDA and 4.10, respectively, under the near ARI humid condition. Most of the total cooling generated by vapor compression heat pump subsystem is used for dehumidification. The moisture removal per kilowatt hour electric power consumption of the system is 1.60-2.88 times that of conventional condensation dehumidification method.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据