期刊
ENERGIES
卷 13, 期 12, 页码 -出版社
MDPI
DOI: 10.3390/en13123274
关键词
ECU; irreversibility; exergy; energy efficiency; high ambient temperature; experimental
资金
- Kuwait University [EM03/19]
This paper assesses the application of the second-law of thermodynamics in a military Environmental Control Unit (ECU) to evaluate the exergy destruction (or irreversibility) in each component when operating at high ambient temperature. Experimental testings were conducted on three ECUs, 1.5 (5.3 kW), 3 (10.6 kW), and 5 (17.6 kW) tons of refrigeration (RT), to assess the potential contribution of each component to enhance the overall energy efficiency of the system, and to determine the feasibility of the thermodynamic model presented herein. The analysis provided for extreme high ambient conditions up to 51.7 degrees C (125 degrees F). The results yielded that the highest irreversibility was associated with compressors (32.4% to 42.5%). This is followed by the heat exchanges (19.6% to 32.9%) in the case of 1.5-RT and 3-RT units, whereas for the 5-RT unit, the highest irreversibility was associated with the evaporator followed by the one of the compressors. In the 3-RT ECU, the condenser's second-law efficiency enhanced due to an additional fan, yet the working refrigerant increased the irreversibility in the expansion device. The second-law analysis recognized the components with the highest exergy destruction and identified the direction to enhance the exergetic efficiency of any ECU operating at high-temperature climate.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐