Applying a variable geometry ejector in a solar ejector refrigeration system

期刊

INTERNATIONAL JOURNAL OF REFRIGERATION
卷 113, 期 -, 页码 187-195

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2020.01.018

关键词

Variable geometry ejector; Solar ejector refrigeration system; Spindle position; Nozzle exit position; R600a

资金

  1. FCT (Fundacao para a Ciencia e Tecnologia), through INEGI, under LAETA [UIDB/50022/2020]
  2. Studentska grantova soutez SGS TUL [21226/2220]

向作者/读者索取更多资源

This paper presents an experimental study of the influence of a variable geometry ejector (VGE) design on the performance of a small-scale, 1.5 kW nominal capacity solar heat driven ejector air-conditioning system under real-life working conditions. Under variable operating conditions (e.g. solar radiation, ambient temperature) fixed geometry ejector performs poorly, therefore the objective of the present work was to prove the benefit of the VGE concept. In the experimentally tested VGE the area ratio through a movable spindle (SP) and the nozzle exit position (NXP) can be adjusted in order to respond to the operating conditions. The results showed very stable operation of the cooling cycle during the experiments. Both NXP, SP had considerable influences on the cooling cycle performance. An optimal NXP was identified, which did not change with various operating conditions. Similarly, SP also showed an optimum; however, the optimum point depended strongly on the operating conditions. The results clearly indicated the benefit of using the VGE design over the fixed geometry. COP improvement was as high as 24% with a maximum of 0.29 corresponding to a cooling capacity of 1.6 kW when compared to a fixed geometry ejector. The study also confirmed the importance of using a variable-speed pump in the ejector cycle. (C) 2020 The Authors. Published by Elsevier Ltd.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据