Evaluation of cold plasma inactivation efficacy against different airborne bacteria in ventilation duct flow

期刊

BUILDING AND ENVIRONMENT
卷 98, 期 -, 页码 39-46

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2015.12.005

关键词

Cold plasma; Inactivation; Air conditional system; Airborne pathogens; In-duct devices; Indoor air quality

资金

  1. HKSAR Government through the Health and Medical Research Fund [12111712]

向作者/读者索取更多资源

A full-size, experimental, ventilation ductwork was designed and set up to measure one-pass inactivation efficacies of a cold plasma installation under various practical environmental conditions. Five types of microorganisms, which are commonly associated with nosocomial infection, including Escherichia coli, Pseudomonas alcaligenes, Staphylococcus epidermidis, Micrococcus luteus and Serratia marcescens, were chosen and tests were conducted at four airstream velocities, ranging from 2 to 7 m/s, and two different relative humidity (R.H.) levels. The inactivation efficacies for the first three types of bacteria varied from 20% to 70%. It is interesting to note that the inactivation efficacy increased with velocity. No detectable inactivation effect was found for M. luteus and S. marcescens. The inactivation efficacy at 90% R.H. dropped to 10% of the value measured at 55% R.H. The negative ion intensities measured near the plasma installation were correlated with the airstream velocities. When compared with data from systems using conventional fibrous filters, the pressure drop measured across the plasma unit was very small. Our experiments showed that cold plasma technology has high potential to be used as an energy-efficient method for disinfection. Limitations of application are also discussed. (C) 2015 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据