4.7 Article

Sensitivity study for the PMV thermal comfort model and the use of wearable devices biometric data for metabolic rate estimation

期刊

BUILDING AND ENVIRONMENT
卷 110, 期 -, 页码 173-183

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.buildenv.2016.10.007

关键词

Personalized comfort model; PMV; Wearable device; Metabolism

向作者/读者索取更多资源

This paper studies the sensitivity of the Predicted Mean Vote (PMV) thermal comfort model relative to its environmental and personal parameters of a group of people in a space. PMV model equations, adapted in ASHRAE Standard 55 Thermal Environmental Conditions for Human Occupancy, are used in this investigation to conduct parametric study by generating and analyzing multi-dimensional comfort zone plots. It is found that personal parameters such as metabolic rate and clothing have the highest impact. However, as these parameters are difficult to estimate or measure, they are usually assumed to be default values (rest conditions and light clothing). In this work, we show the application of the human-in-the loop sensor data of wearable devices to provide a continuous feedback for the averaged metabolism value of building occupants to be used in the PMV calculation. Moreover, we motivate the use of these sensor data to develop a new personalized comfort model. (C) 2016 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据