Simulation and analysis of cascading faults in hybrid AC/DC power grids

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijepes.2019.105492

关键词

Hybrid AC/DC power grids; Cascading faults; Commutation failure; Power flow transfer; DC block; Cascading trip

资金

  1. National Key Research and Development Program of China [2016YFB0900600]
  2. Technology Projects of State Grid Corporation of China [52094017000W]

向作者/读者索取更多资源

With the increasing use of DC transmission in existing AC networks, the possibility of AC and DC circuits running parallel to each other and sharing the same right-of-way or even the same tower is increasing. Cascading fault is a newly emerging fault type in hybrid AC/DC grids which severely threatens the power quality and safe operation of the network. Cascading fault is defined as an event which initiated from a fault in the inverter AC system or an abnormal operation of the DC system which leads to the multiple fault incidents in hybrid AC/DC power grids. In this paper, first, the mechanism and process of cascading fault in hybrid AC/DC grids are described. Subsequently, based on the analysis of several fault cases which may result in cascading faults in AC power grids, the typical characteristics of hybrid AC/DC power grids are demonstrated. The results from the simulation case studies in PSCAD/EMTDC indicate that the cascading fault is initiated from an inverter AC fault which results in a long-lasting communication failure, leading to a DC system block. Afterward, the power flow transfers from the blocked HVDC line to the paralleled AC lines which results in cascading trips in AC lines. Finally, some feasible solutions to prevent the cascading faults in hybrid AC/DC grids are pointed out.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.6
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据