期刊
IEEE TRANSACTIONS ON POWER DELIVERY
卷 34, 期 6, 页码 2163-2172出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TPWRD.2019.2905532
关键词
Geomagnetic disturbance; geomagnetically induced current; geoelectrical field; 3-D ground conductivity model; corridor impact; GIC assessment
Severe Geomagnetic Disturbances (GMD) pose a threat to the reliability of the United States bulk electrical power system. The NERC reliability standard TPL-007 requires transmission planners to assess potential problems in their service territories due to Geomagnetically Induced Currents (GIC) including transformer thermal assessment. If the assessment indicates a vulnerability, the standard requires the development of a corrective action plan to resolve potential issues. GIC calculation accuracy is critical to the assessment. In this paper, the impact of various geoelectric field calculation methods on the accuracy of calculated GICis evaluated by comparing with observations for a geomagnetic storm that occurred on 07-08 September, 2017. The GIC calculation is carried out for a fairly large-scale power system model and the comparison with observation indicates that better results are achieved using magnetotelluric transfer functions that incorporate the effects of 3-D earth conductivity. The results also indicate an improvement in the comparisons when the transfer-function derived E-fields are interpolated between the original survey site locations.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐