Effect of helical surface disc turbulator on thermal and friction characteristics of double pipe water to air heat exchanger

期刊

EXPERIMENTAL HEAT TRANSFER
卷 34, 期 1, 页码 51-67

出版社

TAYLOR & FRANCIS INC
DOI: 10.1080/08916152.2020.1714819

关键词

Nusselt number; helical surface disc turbulators; heat exchanger; thermal enhancement factor

向作者/读者索取更多资源

The study examined the impact of helix angle and pitch ratio of helical surface disc turbulators on the thermal performance of double pipe heat exchangers. It was found that the smallest pitch ratio and highest helix angle resulted in the highest thermo-hydraulic performance, with a thermal enhancement factor of 1.39 at Re = 3,500. Correlations were developed for various parameters based on the test results.
The effect of helix angle and pitch ratio of helical surface disc turbulators on the thermal performance of double pipe heat exchanger are discussed in this study. Tests are performed with air as working fluid for different pitch ratios, numerous helix angles, and various Reynolds number. Water and air are allowed to flow along inner tube and through annulus, respectively. In each case, the thermal enhancement factor is observed to be higher than unit value. Smallest pitch ratio and highest helix angle yield highest thermo-hydraulic performance of 1.39 at Re = 3,500. Correlations are developed for various parameters.