4.7 Article

Experimental performance evaluation of desiccant coated heat exchangers from a combined first and second law of thermodynamics perspective

期刊

ENERGY CONVERSION AND MANAGEMENT
卷 207, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.enconman.2020.112518

关键词

Desiccant coated heat exchangers; Experiments; Second law of thermodynamics; Energy analysis; Exergy analysis; Entropy generation

资金

  1. National Research Foundation (NRF) Singapore under Central Gap Fund Funding Scheme [R-265-000-641-281]

向作者/读者索取更多资源

The electricity-driven vapor-compression air-conditioning system registers around 3-10% second law efficiency under tropical climates due to the coupling between sensible and latent cooling loads. Desiccant coated heat exchangers (DCHEs) are the next-generation technologies that can improve the efficiency of the air-conditioning process by decoupling sensible and latent loads. Existing literature on DCHEs is primarily directed towards material development and performance evaluation from the first law of thermodynamics standpoint. However, to have an insight into the operation of DCHEs concerning its process irreversibility, performing the second law of thermodynamics analysis is necessary. This analysis will pinpoint the causes of irreversibility in the DCHE system and evaluate the useful work destroyed during its cyclic operation. In this paper, we have developed a general steady-state thermodynamic framework to study the performance of DCHEs from a combined first and second law perspective. Experiments were carried out to obtain the thermodynamic state properties of air, water, and desiccant that are necessary to perform energy and exergy analyses. Further, fundamental parametric studies were conducted to understand the influence of different desiccant type, varying operating parameters, and ambient conditions. Key results revealed that the regeneration process contributed to significant entropy generation rates and by reducing the hot water temperature by 10 degrees C, the second law efficiency illustrates improvement of almost two times. Additionally, by selecting to coat the heat exchanger with a composite polymer material instead of silica gel, the second law efficiency of DCHEs is enhanced by around 2.6 times. Lastly, a hybrid air-conditioning system comprising vapor-compression chiller and DCHE records 50% savings in energy consumption and yields two-times higher second law efficiency.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据