Thermodynamic analysis and life cycle assessment of supercritical pulverized coal-fired power plant integrated with No.0 feedwater pre-heater under partial loads

期刊

JOURNAL OF CLEANER PRODUCTION
卷 233, 期 -, 页码 1106-1122

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.jclepro.2019.06.159

关键词

Coal-fired power plant; Life cycle assessment (LCA); Partial load; NOx reduction

资金

  1. National Natural Science Foundation of China [51806159]
  2. National Basic Research Program of China (973 Program) [2015CB251504]
  3. Fundamental Research Funds for the Central Universities [xjj2018061]

向作者/读者索取更多资源

With ever increasing share of renewable energy sources in the electricity mix, pulverized coal-fired power plants (PCPP) have to participate in peak load regulations frequently and thus, they regularly operate under partial loads. The energy efficiency and eco-efficiency are both significantly affected by such operating patterns. Therefore, the present work aims to establish an overall concept for the estimation of environmental impacts from PCPP under nominal and partial loads with combined thermodynamic analysis and life cycle assessment (LCA) methodology. A 1000 MW supercritical PCPP was modeled using commercial simulation software (GSE for thermodynamic simulation and SimaPro for LCA analysis). Results indicated that global warming was the predominant environmental impact of PCPP, while ozone formation, acidification and eutrophication were also serious concerns attributed to NOx emissions in electricity generation process. The mechanisms of formation, migration and removal of different kinds of pollutant emissions significantly influenced the LCA results. Particularly, the total environmental impact potential considerably increased by approximately 90% under partial/low loads due to reductions in the plant thermal efficiency and NOx removal efficiency. A novel partial load No.0 feedwater preheating system driven by steam ejector was thus proposed for NOx reduction improvement. Operation optimization was carried out based on the guidelines of the LCA framework. It was found that the total environmental impact could be effectively reduced by up to 27.3%. Therefore, the implementation of the No.0 feedwater pre-heater was favorable for environmental performance improvement under partial/low loads. (C) 2019 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据