4.7 Article

Experimental research on the heat transfer and water recovery performance of transport membrane condenser

期刊

APPLIED THERMAL ENGINEERING
卷 160, 期 -, 页码 -

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2019.114060

关键词

Transport membrane condenser; Latent heat; Convective heat transfer coefficient; Flue gas

资金

  1. National Key R&D Program of China [2018YFB0604302]
  2. Top-notch Innovative Personnel Development Program of NCEPU [XM1805311]

向作者/读者索取更多资源

Transport membrane condenser (TMC) is a device for extracting moisture and heat from the exhaust. This paper designs a TMC which contains 46 ceramic membrane tubes to treat the exhaust from a gas-fired boiler. The trends of the recovered water flux, the convective heat transfer coefficient, and latent and sensible heat under different experimental conditions are investigated. The experimental results show that the heat transfer and water recovery performance of the TMC can be increased by increasing the flowrate of flue gas and cooling water, and increasing the temperature difference between flue gas and cooling water. Compared with other studies, the novelty of this paper is reflected in two aspects. Firstly, using TMC consisting of ceramic membranes with the pore size of 1 mu m can recover more water than traditional TMC. Secondly, the convective heat transfer coefficient, latent heat and sensible heat released by flue gas are calculated quantitatively under different working conditions. The maximum recovered water flux is 15.77 kg/(m(2) h), and the latent heat released by condensation accounts for more than 75% of the total heat released by the flue gas.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据