4.7 Article

Numerical simulation of water spray in natural draft dry cooling towers with a new nozzle representation approach

期刊

APPLIED THERMAL ENGINEERING
卷 98, 期 -, 页码 924-935

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2015.10.118

关键词

Spray cooling; Air pre-cooling; Natural draft; Spray representation; Rosin-Rammler

资金

  1. Saudi Arabian Government (King Abdulaziz City for Science and Technology (KACST))
  2. Queensland Geothermal Energy Centre of Excellence (QGECE)

向作者/读者索取更多资源

Pre-cooling of inlet air with water spray is proposed for performance enhancement of natural draft dry cooling towers (NDDCTs) during high ambient temperature periods. Previous experiments showed promising results on cooling enhancement using spray cooling. In this study, a numerical Eulerian-Lagrangian 3-D model is used to simulate evaporating water sprays produced by real nozzles. A new adaptable method of hollow-cone spray representation in Eulerian-Lagrangian numerical models was developed to reproduce the real nozzle behaviour using experimentally measured initial spray characteristics and taking into account radial evolution of droplet size distribution and air/droplets momentum exchange. Experimental measurements from a wind tunnel test rig simulating NDDCT5 inlet flow conditions have been performed for validation. Overall, a good agreement was obtained between numerical predictions and experimental measurements for the streamwise development of droplet size and velocity, and outlet air dry bulb temperature. An average deviation below 5.3% was achieved for all compared parameters. Moreover, the validated CFD model has provided insight into the experimental observations of local droplet velocity increase and higher air cooling in the lower region. (C) 2015 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据