4.7 Article

Exergetic, energetic and financial evaluation of a solar driven absorption cooling system with various collector types

期刊

APPLIED THERMAL ENGINEERING
卷 102, 期 -, 页码 749-759

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2016.04.032

关键词

Solar cooling; Absorption chiller; Exergy analysis; Financial evaluation

资金

  1. Onassis Foundation

向作者/读者索取更多资源

Solar energy utilization for cooling applications is analyzed in this study. A single effect absorption chiller operating with LiBr-H2O is the cooling sorption machine which is coupled with a collector field. The cooling demand is 100 kW at 10 degrees C for Athens (Greece) in summer. Four different collector types are tested in order to predict the most suitable solution for this study case. More specifically, flat plate collectors, evacuated tube collectors, compound parabolic collectors and parabolic trough collectors are investigated under the same conditions. An exergetic optimization of every system gives the optimum solution of every case, which leads to minimum collecting area. A financial comparison between the four optimized systems proves that evacuated tube collectors are the most beneficial technology. On the other hand, system with parabolic trough collectors is the exergetic optimum one, but its high capital cost renders it an unprofitable solution. The analysis is made in steady state conditions with Engineer Equator Solver (EES), a very useful energy tool. (C) 2016 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据