4.7 Article Proceedings Paper

Development and validation of a CFD model for numerical simulation of a large natural draft wet cooling tower

期刊

APPLIED THERMAL ENGINEERING
卷 105, 期 -, 页码 953-960

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2016.03.020

关键词

Cooling tower; CFD model; Fluent; Validation; Test facility

向作者/读者索取更多资源

Electricite de France (EDF) has commissioned the development of a CFD model, based on ANSYS Fluent v.16, which includes the specific equations (Poppe and Merkel) describing the physical phenomena occurring in a natural draft wet cooling tower (NDWCT). Heat and mass transfers between water and air, as well as drag equations for the two-phase system, are computed in specific zones such as the cooling fill, spray and rain zones. This paper presents the CFD model created and the two-step methodology implemented for the validation process: The model is first tested and set regarding thermal performance results obtained on EDF test cell Mistral located on the Bugey site. The Mistral facility includes a 7m x 7m counter-flow section, equipped with a large number of temperature and pressure sensors, which represents an efficient and reliable mean for cooling fill performances evaluation. Secondly, the model is fully validated thanks to acceptance tests results gathered from a large scale NDWCT refurbishment. To this end, advanced instrumentation was positioned in the tower to provide additional data for extensive validation of the model. (C) 2016 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据