4.7 Article

Experimental and numerical analysis for effects of using conical ring on turbulent flow and heat transfer in a double pipe air to water heat exchanger

期刊

APPLIED THERMAL ENGINEERING
卷 100, 期 -, 页码 805-819

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.applthermaleng.2016.02.075

关键词

Perforated conical ring; Air to water heat exchanger; NSGA II; Pressure loss; Heat transfer; CFD

向作者/读者索取更多资源

Effect of typical and perforated conical ring turbulators on hydrothermal behavior of air to water double pipe heat exchanger is investigated. Two arrays (Direct conical ring (DCR) array and Reverse conical ring (RCR) array) are considered. Experimental analysis is examined for different values of open area ratio (0-0.0833), Reynolds number (6000-12,000), conical angle (0 degrees-30 degrees) and pitch ratio (1.83-5.83). Correlations for friction factor, Nusselt number and thermal performance factor are presented. To reach the optimal design, Non Sorting Genetic Algorithm II is applied. Pareto front of optimized solution is presented. Also the finite volume method (commercial code) is utilized for numerical section in order to show physical phenomena. Results indicate that friction factor reduces with augment of open area ratio, pitch ratio and Reynolds number. Nusselt number reduces with increase of open area ratio and pitch ratio while it augments with enhance of Reynolds number. Also it can be concluded that thermal performance rises with augment of conical angle for direct conical ring array. (C) 2016 Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据