4.5 Article

Effects of ground heat exchangers with different connection configurations on the heating performance of GSHP systems

期刊

GEOTHERMICS
卷 80, 期 -, 页码 20-30

出版社

PERGAMON-ELSEVIER SCIENCE LTD
DOI: 10.1016/j.geothermics.2019.02.002

关键词

Ground source heat pump; Ground heat exchanger; Connection configurations; Coefficient of performance

资金

  1. National Natural Science Foundation of China [51641608]
  2. China Scholarship Council Foundation

向作者/读者索取更多资源

The connection configurations of ground heat exchangers (GHEs) have a significant impact on the ground temperature and the performance of ground source heat pump (GSHP) systems. In this paper, the heating performance of a GSHP system implemented in a net zero-energy building with two different GHE connection configurations, including series and parallel connections, was experimentally and numerically investigated. A mathematical model was developed based on ANSYS fluent to analyze the thermal performance of the GHEs and the model was validated against the experimental data. The experimental results showed that the parallel configuration of the GHEs achieved a better heating performance when the mass flow rate was 2.58 kg.s(-1), as compared to that of the series configuration. The system heating performance with both series and parallel configurations of the GHEs increased with the decrease in the fluid flow rate under the same heating load condition. The pressure drop between the inlet and outlet of the GHEs with the series configuration was also higher when compared to that with the parallel configuration.