4.8 Article

Experimental investigation of a ground-coupled desiccant assisted air conditioning system

期刊

APPLIED ENERGY
卷 181, 期 -, 页码 575-585

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.apenergy.2016.08.036

关键词

Desiccant wheel; Air conditioning; Borehole heat exchanger; Experimental

资金

  1. Federal Ministry for Economic Affairs and Energy [03ET1065A]

向作者/读者索取更多资源

In a pilot installation at Hamburg University of Technology the coupled operation of an open cycle desiccant assisted air conditioning system with borehole heat exchangers is investigated. The paper presents experimental data recorded during the cooling period 2014. Results show that the electricity demand of the system can be reduced to the parasitic consumption of the fans, wheels and pumps. An electric energy efficiency ratio of 6.63 is achieved, enabling electricity savings of more than 70% compared to a conventional reference system and 54% compared to a desiccant assisted hybrid system relying on an electric chiller. Comfort conditions can be maintained during the whole cooling period. The borehole heat exchangers work highly efficient, exhibiting a seasonal performance factor of 192. (C) 2016 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.8
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据