4.7 Article

An improved approach for robust control of dynamic voltage restorer and power quality enhancement using grasshopper optimization algorithm

期刊

ISA TRANSACTIONS
卷 95, 期 -, 页码 110-129

出版社

ELSEVIER SCIENCE INC
DOI: 10.1016/j.isatra.2019.05.001

关键词

Disturbance rejection; Dynamic voltage restorer; PID controller; FOPID controller; Power quality; Harmonic distortion; Stochastic optimization

向作者/读者索取更多资源

This paper presents a novel contribution of a low complexity control scheme for voltage control of a dynamic voltage restorer (DVR). The scheme proposed utilizes an error-driven proportional-integral-derivative (PID) controller to guarantee better power quality performance in terms of voltage enhancement and stabilization of the buses, energy efficient utilization, and harmonic distortion reduction in a distribution network. This method maintains the load voltage close to or equal to the nominal value in terms of various voltage disturbances such as balanced and unbalanced sag/swell, voltage imbalance, notching, different fault conditions as well as power system harmonic distortion. A grasshopper optimization algorithm (GOA) is used to tune the gain values of the PID controller. In order to validate the effectiveness of the proposed DVR controller, first, a fractional order PID controller was presented and compared with the proposed one. Further, a comparative performance evaluation of four optimization techniques, namely Cuckoo search (CSA), GOA, Flower pollination (FBA), and Grey wolf optimizer (GWO), is presented to compare between the PID and FOPID performance in terms of fault conditions in order to achieve a global minimum error and fast dynamic response of the proposed controller. Second, a comparative analysis of simulation results obtained using the proposed controller and those obtained using an active disturbance rejection controller (ADRC) is presented, and it was found that the performance of the optimal PID is better than the performance of the conventional ADRC. Finally, the effectiveness of the presented DVR with the controller proposed has been assessed by time-domain simulations in the MATLAB/Simulink platform. (C) 2019 ISA. Published by Elsevier Ltd. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据