4.5 Article

Experimental study of the heat transfer in R744/R600a mixtures below the R744 triple point temperature

出版社

ELSEVIER SCI LTD
DOI: 10.1016/j.ijrefrig.2019.03.038

关键词

Carbon dioxide; Isobutane; Natural refrigerants; Heat transfer; Dry ice; Sublimation

资金

  1. Faculty of Building Services, Hydro and Environmental Engineering, Warsaw University of Technology [504/02101/1110/42.000100, 504/02646/1110/42.000100]

向作者/读者索取更多资源

Carbon dioxide, a natural refrigerant, is attracting attention as a direct solution to the legal restrictions on hydrofluorocarbon (HFC) refrigerants. The use of carbon dioxide as a refrigerant is limited by the triple point temperature of -56.5 degrees C. However, used along with a carrier fluid, carbon dioxide can provide refrigeration to temperatures lower than the triple point. A blend composed of carbon dioxide (R744) and isobutane (R600a) is experimentally studied. An experimental setup was designed, built, and verified in order to obtain the sublimation heat transfer coefficients of R744/R600a mixtures at temperatures lower than -56.5 degrees C. The test section comprises a horizontal copper tube with an inner diameter of 10 mm and length of 1 m. The tube is electrically heated by a copper wire heater wrapped uniformly around the tube. The tests were conducted with a novel refrigerant blend at heat fluxes from 3630 W m(-2) to 8480 W m(-2). The heat transfer coefficient decreases with increasing heat flux. Furthermore, a heat transfer coefficient calculation correlation has been developed. (C) 2019 Elsevier Ltd and IIR. All rights reserved.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.5
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据