期刊
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT
卷 68, 期 5, 页码 1322-1332出版社
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
DOI: 10.1109/TIM.2018.2880060
关键词
Harmonics; instrument transformers (ITs); power quality; power system measurement; uncertainty
This paper aims at characterizing and improving the metrological performances of current and voltage instrument transformers (CTs and VTs) in harmonic measurements in the power system. A theoretical analysis is carried out to demonstrate that, due to the iron core nonlinearity, CT and VT output signal is distorted even when the input signal is a pure sine wave. Starting from this analysis, a new method for CT and VT characterization and compensation is proposed. In a first step, they are characterized in sinusoidal conditions and the harmonic phasors of the distorted output are measured; in the second step, these phasors are used to compensate the harmonic phasors measured in normal operating conditions, which are typically distorted. The proposed characterization and compensation techniques are called SINusoidal characterization for DIstortion COMPensation (SINDICOMP). Several experimental tests, using high-accuracy calibration setups, have been performed to verify the proposed methods. The experimental results showed that the SINDICOMP technique assures a significant improvement of CT and VT metrological performances in harmonic measurements.
作者
我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。
推荐