4.7 Article

Design and analysis of a combined desalination and standalone CCHP (combined cooling heating and power) system integrating solar energy based on a bi-level optimization model

期刊

SUSTAINABLE CITIES AND SOCIETY
卷 43, 期 -, 页码 166-175

出版社

ELSEVIER
DOI: 10.1016/j.scs.2018.08.023

关键词

Bi-level optimization; Standalone CCHP system; Seawater desalination; PVT panels; MILP problem

资金

  1. National Key Research Projects [2016YFC0207800]
  2. National Natural Science Foundation of China [51590911, 51608422]
  3. Xi'an University of Architecture and Technology [6040318066]

向作者/读者索取更多资源

Water and energy supply are strongly interrelated on islands without power grid infrastructure and their efficient management can be achieved by integrating seawater desalination and solar energy into combined cooling, heating, and power (CCHP) systems. In this study, a bi-level optimization methodology is proposed to optimize a combined desalination and standalone CCHP system, which is assumed as installed on a remote South China Sea island. The traversing method and branch-and-bound method are used for solving the mixed-integer linear programming (MILP) optimization problem at the design and operation stages, respectively. The results indicate that the economic and environmental objectives determine the system configuration with the minimum and maximum capacity of each component. As the system configuration changes, the system energy efficiency exhibits a consistent change tendency with the carbon dioxide emission generally. It is also observed that the capacity of the electrical storage system (ESS) is no larger than that of the thermal storage system (TSS) because of the relative high cost-performance ratio of the ESS. The integrated desalination with the water tank proves to be effective for improving the system performance.

作者

我是这篇论文的作者
点击您的名字以认领此论文并将其添加到您的个人资料中。

评论

主要评分

4.7
评分不足

次要评分

新颖性
-
重要性
-
科学严谨性
-
评价这篇论文

推荐

暂无数据
暂无数据